Link-up and update
8.3 Time monitoring
CPU 410-5H Process Automation
134 System Manual, 09/2014, A5E31622160-AB
8.3.4
Influences on time response
The period during which no I/O updates take place is primarily determined by the following
influencing factors:
The number and size of data blocks modified during the update
The number of instances of SFBs in S7 communication and of SFBs for generating block-
specific messages
System modifications during operation
Expansion of distributed I/Os with PROFIBUS DP (a lower baud rate and higher number
of slaves increases the time it takes for I/O updates).
Expansion of distributed I/Os with PROFINET IO (a higher update time and higher
number of devices increases the time it takes for I/O updates).
In the worst case, this period is extended by the following amounts:
Maximum cyclic interrupt used
Duration of all cyclic interrupt OBs
Duration of high-priority interrupt OBs executed until the start of interrupt delays

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 CPU 410-5H and is the answer not in the manual?

Siemens SIMATIC PCS 7 CPU 410-5H Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7 CPU 410-5H
CategoryController
LanguageEnglish

Related product manuals