Supplementary information
15.15 Cycle and response times of the CPU 410-5H
CPU 410-5H Process Automation
320 System Manual, 09/2014, A5E31622160-AB
15.15.9
Reproducibility of delay and watchdog interrupts
Definition of "reproducibility"
Time-delay interrupt:
The period that expires between the call of the first operation in the interrupt OB and the
programmed time of interrupt.
Cyclic interrupt:
The fluctuation range of the interval between two successive calls, measured between the
respective initial operations of the interrupt OB.
Reproducibility
The following table contains the reproducibility of time-delay and cyclic interrupts of the
CPUs.
Table 15- 20 Reproducibility of time-delay and cyclic interrupts of the CPUs
Module Reproducibility
Time-delay interrupt
Cyclic interrupt
CPU 410-5H stand-alone mode ± 120 µs ± 160 µs
CPU 410-5H redundant
± 200 µs
± 180 µs
These times only apply if the interrupt can actually be executed at this time and if it is not
delayed, for example, by higher-priority interrupts or queued interrupts of equal priority.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 CPU 410-5H and is the answer not in the manual?

Siemens SIMATIC PCS 7 CPU 410-5H Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7 CPU 410-5H
CategoryController
LanguageEnglish

Related product manuals