Structure of the CPU 410-5H
3.3 Status and error displays
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
43
The LINK and RX/TX LEDs indicate the current state of the PROFINET IO interfaces.
Table 3- 3 Possible states of the LINK and RX/TX LEDs
Lit Irrelevant Connection at the PROFINET IO interface is active
Irrelevant Flashes
Receiving or sending data at the PROFINET IO interface.
Note
The LINK and RX/TX LEDs are located dir
ectly next to the sockets of the PROFINET IO
interfaces. They are not labeled.
The REDF LED indicates specific system states and redundancy errors.
Flashes
Link-up -
Flashes
Update -
Redundant (CPUs are redundant)
Lit Redundant (CPUs are redundant) There is an I/O redundancy error:
• Failure of a DP master, or partial or total failure of a
DP master system
• Failure of a PN IO subsystem
• Loss of redundancy on the DP slave
• Loss of redundancy at the PN IO device
• Loss of redundancy on the DP slave/slave failure
• Loss of redundancy at the PN IO device/device
failure