System modifications during redundant operation
10.4 Removal of components
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
167
10.4.1
Step 1: Modify the hardware configuration offline
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1. Perform offline only the configuration modifications relating to the hardware being
removed. As you do, delete the icons to the channels that are no longer used.
2. Compile the new hardware configuration, but do
not
load it into the target system just yet.
Result
The modified hardware configuration is in the PG/ES. The target system continues operation
with the old configuration in redundant system mode.