11 – 9
11.10 Updating the options label
NOTE
After installing additional electrical components, mark with a "x", using an indelible ink pen.
The voltage must also be noted in the box.
Closing coil VAC 50/60 Hz VDC Catalog No.
Closing coil
— 24 WLRCS24
— 48 WLRCS48
110-127 110-125 WLRCS120
208-240 220-250 WLRCS240
Signaling switches Catalog No.
Signaling switch for 1st shunt trip WLSTC
Signaling switch for 2nd shunt trip or undervoltage release WLUVRC
1st Shunt Trip VAC 50/60 Hz VDC Catalog No.
Shunt trip F1
— 24 WLST24
— 48 WLST48
110-127 110-125 WLST120
208-240 220-250 WLST240
2nd Shunt Trip or UVR VAC 50/60 Hz VDC Catalog No.
Shunt trip F2
— 24 WLST24
— 48 WLST48
110-127 110-125 WLST120
208-240 220-250 WLST240
Undervoltage release F3 (instantaneous)
— 24 WLUV24
— 48 WLUV48
110-127 110-125 WLUV120
208-240 220-250 WLUV240
Undervoltage release F4 (time-delayed)
— 48 WLUVD48
110-127 110-125 WLUVD120
208-240 220-250 WLUVD240
Siemens Industry, Inc., Fort Worth, TX 76155 USA
Charging Motor
Remote Close Coil
X5-2 (+)
X5-1 (-)
X6-7 (+)
X6-8 (-)
240
250
VAC
VDC
120
125
VAC
VDC
240
250
VAC
VDC
120
125
VAC
VDC
VAC
VDC
120
125
VAC
VDC
1st Shunt Trip
UVR
2nd Shunt Trip
Remote Reset
X6-13 (-)
X6-14 (+)
X5-11 (-)
X5-12 (+)
X9-1 (-)
X9-2 (+)
X8-13 (-)
X8-14 (+)
Ready to Close Switch
X6-5
X6-6
240 VAC
4A
240 VAC
1st Shunt Trip Switch
X9-7
X9-8
240 VAC
240 VAC
UVR Switch
Open Fuse Switch
X9-10
X9-11
X9-5
X9-6
52a 1st Aux. SW. 52b
X6-3
X6-4
X6-11
X6-12
X6-1
X6-2
X6-9
X6-10
X5-5
X5-6
X5-9
X5-10
X5-3
X5-4
X5-7
X5-8
52a 2nd Aux. SW. 52b
240 VAC ,
Bell Alarm
240 VAC
5A
5A
X9-13
X9-14X9-12
3A
3A
Assembled in USA
10 A / 125 VDC , 0.5 A / 24 VDC , 3A
0131-FW