6 – 6
6.3 Check list for commissioning
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
Action required
q
Verify the circuit breaker is OPEN
Verify the rating plug is installed
Rating plug (page 9-44)
Verify the TRIP indicator is reset
Set the trip unit to appropriate values
Trip units (page 9-1)
Apply secondary and control voltages
Close the cubicle door
Rack circuit breaker into connected position
Push in the racking handle
Charge closing spring
Ensure the following conditions exist
Undervoltage release energized
Locking devices not activated
Indicators