24 – 1
24 Technical Data
WL Power Circuit Breaker
Ratings for UL 1066 Listed (ANSI C37) Breakers
1) Maintenance means: replacing main contacts and arc chutes (see operating instructions)
M-Class main contacts can be replaced by Siemens personnel only.
2) Short-time Withstand Current I
CW
at 635VAC is 85 kAIC RMS
3) max. 600 V AC
WL frame ratings – Frame size 2 800A 1600A
Rating Class N S H L F N S H L F
Interrupting current frame Ics (kAIR RMS) 50/60 Hz 254VAC 50 65 85 100 200 50 65 85 100 200
508VAC 50 65 85 100 200 50 65 85 100 200
600VAC — — 200 — — 200
635VAC 50 65 65 85 50 65 65 85
Short-time current Icw (kA RMS) 1 sec. 50 65 65 85 50 65 65 85
Close and latch rating (kA RMS) 50 65 65 85
50 65 65 85
Applicable rating plug range 200 - 800A 200 - 1600A
Mechanical make-time (ms) 35 35
Mechanical break-time (ms) 34 34
Electric close make-time (ms) 50 50
Electric trip/ UV break-time (ms) 40/73 40/73
Electric trip and reclose interval (ms) 80 80
Mechanical duty cycles (no maint.) 15,000 15,000
Electrical duty cycles (no maint) 15,000 15,000
Draw-out breaker efficiency (Watts loss at rated I
n) 85 320
Draw-out fused breaker efficiency (Watts loss at rated I
n) Consult factory Consult factory
Ambient operating temperature (ºC) -25 to 40 -25 to 40
Weights (Fused Breaker/Breaker/Cradle) lbs. 227/159/112 227/159/112
WL frame ratings – Frame size 2 2000A 3200A
Rating Class S H L F S H L
Interrupting current frame Ics 254VAC 65 85 100 200 65 85 100
(kAIR RMS) 50/60 Hz 508VAC 65 85 100 200 65 85 100
600VAC 200
635VAC 65 65 85 65 65 85
Short-time current Icw (kA RMS) 1 sec. 65 65 85 65 65 85
Close and latch rating (kA RMS) 65 65 85 65 65 85
Applicable rating plug range 200 - 2000A 200 - 3200A
Mechanical make-time (ms) 35 35
Mechanical break-time (ms) 34 34
Electric close make-time (ms) 50 50
Electric trip/ UV break-time (ms) 40/73 40/73
Electric trip and reclose interval (ms) 80 80
Mechanical duty cycles (no maint.) 15,000 15,000
Electrical duty cycles (no maint) 15,000 15,000
Draw-out breaker efficiency (Watts loss at rated I
n) 700 1650
Draw-out fused breaker efficiency (Watts loss at rated I
n) Consult factory Consult factory
Ambient operating temperature (ºC) -25 to 40 -25 to 40
Weights (Fused Breaker/Breaker/Cradle) lbs. 227/209/152 227/209/152
WL frame ratings – Frame size 2 800A 1600A
Rating Class N S H L F N S H L F
Interrupting current frame Ics (kAIC RMS) 50/60 Hz 254VAC 50 65 85 100 200 50 65 85 100 200
508VAC 50 65 85 100 200 50 65 85 100 200
600VAC — — 200 — — 200
635VAC 50 65 65 85 50 65 65 85
Short-time current Icw (kA RMS) 1 sec. 50 65 65 85 50 65 65 85
Close and latch rating (kA RMS) 50 65 65 85
50 65 65 85
Applicable rating plug range 200 - 800A 200 - 1600A
Mechanical make-time (ms) 35 35
Mechanical break-time (ms) 34 34
Electric close make-time (ms) 50 50
Electric trip/ UV break-time (ms) 40/73 40/73
Electric trip and reclose interval (ms) 80 80
Mechanical duty cycles (with maint.
1
) 15,000 15,000
Electrical duty cycles (with maint.
1
) 15,000 15,000
Draw-out breaker efficiency (Watts loss at rated I
n
) 85 320
Draw-out fused breaker efficiency (Watts loss at rated I
n
) Consult factory Consult factory
Ambient operating temperature (ºC) -25 to 40 -25 to 40
Weights (Fused Breaker/Breaker/Cradle) lbs. 227/159/112 227/159/112
WL frame ratings – Frame size 2 2000A 3200A
Rating Class S H L F S H L
Interrupting current frame Ics 254VAC 65 85 100 200 65 85 100
(kAIC RMS) 50/60 Hz 508VAC 65 85 100 200 65 85 100
600VAC — 200
635VAC 65 65 85 65 65 85
Short-time current Icw (kA RMS) 1 sec. 65 65 85 65 65 85
Close and latch rating (kA RMS) 65 65 85 65 65 85
Applicable rating plug range 200 - 2000A 200 - 3200A
Mechanical make-time (ms) 35 35
Mechanical break-time (ms) 34 34
Electric close make-time (ms) 50 50
Electric trip/ UV break-time (ms) 40/73 40/73
Electric trip and reclose interval (ms) 80 80
Mechanical duty cycles (with maint.
1
) 15,000 15,000
Electrical duty cycles (with maint.
1
) 15,000 15,000
Draw-out breaker efficiency (Watts loss at rated I
n
) 700 1650
Draw-out fused breaker efficiency (Watts loss at rated I
n
) Consult factory Consult factory
Ambient operating temperature (ºC) -25 to 40 -25 to 40
Weights (Fused Breaker/Breaker/Cradle) lbs. 227/209/152 227/209/152