178 RemotEye 4 User Manual – 90988-007
APPENDIX D – BACNET POINT MAPPING FOR 4400
D.1 BACNET ANALOG INPUT POINT MAPPING FOR 4400
ALL – BACnet Object: Analog Input BACnet Property: Present Value Out of Service: FALSE
Access: Read Only Status Flags: Normal
4400 BACnet Analog Input Point Mapping
Object Name & Description
RMTI
-4 System
Information
RemotEye 4 Software Version
RemotEye 4 Slave ID Number
RemotEye 4 Installation Date
UPS Display Firmware Version
Input Voltage Phase AB (L-L)
Input Voltage Phase BC (L-L)
Input Voltage Phase CA (L-L)
Input Voltage Phase AN (L-N)
Input Voltage Phase BN (L-N)
Input Voltage Phase CN (L-N)
Input Voltage Percent Phase A
Input Voltage Percent Phase B
Input Voltage Percent Phase C
Input Rated Voltage (L-L)
Input Rated Voltage (L-N)