RemotEye 4 User Manual – 90988-007 25
INSTALL REMOTEYE 4 IN UPS
Follow these steps to install the RemotEye 4 card.
1. Record the RemotEye 4 PCB MAC address (see Figure 3-1 ) in Table 3-1 before physically installing the
PCB in the UPS.
(For each RemotEye 4, the MAC address is created using the following format: 00 E0 D8 LL MM NN.
The first half of this code, 00 E0 D8, identifies the manufacturer of the Ethernet board. Since every
RemotEye 4 is produced by the same manufacturer, these 3 hexadecimal bytes remain constant. The LL
MM NN characters identify the serial number of the device in hexadecimal form. The serial number is
unique for each RemotEye 4 device.)
Figure 3-1 RemotEye 4 MAC Address Location
2. Ensure the UPS is turned off using the proper shutdown procedure as explained in the UPS manual.
3. Slide the RemotEye 4 card assembly into the RemotEye 4 slot of the UPS. (see Figure 3-2 thru Figure
3-4)
4. Secure the RemotEye 4 card assembly using the factory-supplied screws.
Figure 3-2 RemotEye 4 Location in 1600XP