54 RemotEye 4 User Manual – 90988-007
Figure 6-10 BACnet Settings for BACnet MS/TP
8. Set the BACnet master port parameters:
8.1. COM Port
8.2. Baud Rate:
8.3. Station
8.4. Max Master
Note: For additional RS-485 Connection Information, reference Appendix P
6.3.3 Suggested Communication Settings
All Protocols (Modbus TCP, Modbus RTU, BACnet MS/TP, BACnet IP):
Reply Timeout: 500ms
Delay Time: 1 second
Min Delay between polls:
If you set this value lower than 1 second the time gap between response and a new request cannot be
guaranteed. This is because the scheduler switch tasks every 10 - 20ms.