3 Select Manager from the Log on as drop down menu.
4 Enter the password into the Password field. Default password is 123456
5 Click the Login button. The SUS program will open. The bottom of the screen will say No Device
Connected.
6 Connect the PDA to the AD-300 lock using the supplied USB cable.
7 Press the Schlage button twice on the AD-300 keypad. The bottom of the PDA screen will now display
AD300.
8 Click on the Options button at the bottom of the PDA screen. A list of options will open.
9 Put the AD-300 lock into Pairing Mode (this is necessary for the PDA to be able to make changes to the
lock's settings).
10 Hold down the Internal Push Button on the AD-300 lock.
11 While holding down the Internal Push Button, click the Tamper Switch (SW1) three times on the AD-
300 lock. The red LEDs in the Schlage button will flash.
12 On the PDA click the Pair PDA to Device option. A pop-up will display when the pairing process is
complete.
13 Click on the Lock Properties option.The Lock Properties window will open.
14 Click on the Edit tab.
15 Click on the RS485 Address field. A touch-keyboard will open at the bottom of the screen.
16 Using the touch-keyboard, enter in the address of the lock.
17 Click on the Save button at the bottom of the screen. After a moment the Properties Saved
Successfully pop-up will open.
18 Either click OK on the pop-up, or wait a moment and it will close on its own. The lock has been addressed.
19 Make a note of the address, it will be required to set up the lock in the software.