Wireless reader modules configuration
The Schlage Wireless Configuration & Demonstration Tool (CDT) must be used to assign each PIM-SBB an
address and to address each WAPM connected to it.
A maximum of sixteen (16) wireless readers can communicate with a PIM module on the same channel, with all
reader types. Address can be 0 through 15 (panel number 0 to 15 in the CDT). Example - if a WAPM is
configured as Panel 5 (door 5) using the CDT, then its corresponding address in bright blue is five (5).
Note: All other devices use address 1 through 16. Do not allow the device addresses to overlap when using non-
wireless devices in tandem with wireless devices. Example: wireless devices using addresses 0 through 10
require any non-wireless devices to start their addressing at 12.
Device capacities
PIM-SBB (Legacy) modules
â–ª Contact 1 - PIM module
â–ª Tamper state - NC
WAPM modules
â–ª Relay 1 for the lock
â–ª Relay 1 state will be reported back to bright blue
▪ Contact 1 for REX – Normally Open, Non-supervised
▪ Contact 2 for DOD – Normally Open, Non-supervised
▪ Contact 3 for Tamper – NC, Non-supervised
▪ Contact 4 for Battery – NC, Non-supervised
▪ Contact 5 for Motor – NC, Non-supervised (Currently not applicable)
â–ª Contact 6 for Request to Enter - NC, Non-supervised
WRI
â–ª Relay 1 for the lock
â–ª Relay 1 state will be reported back to bright blue
â–ª Relay 2 for Aux Relay
â–ª Relay 2 state will not be reported to the bright blue
▪ Contact 1 for REX – Normally Open, Non-supervised
▪ Contact 2 for DOD – Normally Open, Non-supervised
▪ Contact 3 for Tamper – NC, Non-supervised
Linking and addressing locks to the PIM
Requirements - PIM CDT RS-232 cable to the serial port on the PC running the CDT program.