EasyManuals Logo
Home>Xinje>Servo Drives>DS5E Series

Xinje DS5E Series User Manual

Xinje DS5E Series
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
80
Because it can only rotate in one direction, after a certain period of time, the number of revolving
cycles will always exceed the upper limit of absolute value encoder.
Servo motor
series
Resolution
(single-circle
data)
Rotating Circle
Serial Data
Output range
Operation of overtime
CM/T
17
-32768~32767
When it is higher than the upper limit value
in the forward direction (+32767*2^ 17):
Rotation serial data = 32767*2^17
When it is below the lower limit of reversal
direction (-32768*2^ 17):
Rotation Serial Data=-32767*2^17
TL
23
When it is higher than the upper limit value
in the forward direction (+32767*2^23):
Rotation serial data = 32767*2^23
When it is below the lower limit of reversal
direction (-32768*2^ 23):
Rotation Serial Data=-32767*2^23
5.11.4 Read absolute position through communication
Basic parameters
User
parameter
Name
Use
U0-10
encoder feedback value
Absolute value single-loop position, read 0x100A
hexadecimal address through Modbus RTU
double-word, which is the current encoder single-loop
position;
U0-11
U0-91
present circles of multi-loop
absolute
The hexadecimal address of 0x105F is read by Modbus
RTU double word, which is the current encoder position.
U0-57
absolute encoder present
position feedback low 32-bit
The hexadecimal address of 0x1039 is read by Modbus
RTU double word, which is the current encoder position
with positive and negative pulses.
U0-58
U0-59
absolute encoder present
position feedback high 32-bit
The hexadecimal address of 0x1041 is read by Modbus
RTU double word, which is the high position of the
current encoder, low bit data is needed.
U0-60
F1-06
Clear the absolute encoder
circles
Write 1 to the hexadecimal address of 0x2106 through
Modbus RTU to clear the cycles (servo BB status takes
effect, and write 0 to 0x2106 after clearance);
Servo driver transmits position data information of encoder through RS485 port and Modbus RTU
protocol.
17-bit absolute value encoder has 131072 pulses per cycle.
First read the U0-60 (0x1041) value
(1) 0 means running in the positive direction. The current position of the encoder is
U0-57*1+U0-58*2^16.
(2) 1 means running in the opposite direction. The current encoder value is: (U0-57-65535)*1+
(U0-58-65535)*2^16.
If the position is read by XINJE HMI and the U0-57 (Modbus address is decimal 4153) double-word is
read, the high-low byte exchange should be selected. If communicating with Xinje PLC, direct
double-word reading is ok.
23-bit absolute value encoder, one-cycle pulse number is 8388608.

Table of Contents

Other manuals for Xinje DS5E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje DS5E Series and is the answer not in the manual?

Xinje DS5E Series Specifications

General IconGeneral
BrandXinje
ModelDS5E Series
CategoryServo Drives
LanguageEnglish

Related product manuals