ELECTRICAL INSTALLATION
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
142/266
5. If the outer cable screen is conductive, remove the cable insulation at the
point of entry (1 in Fig. 6-28).
If the outer cable screen is non-conductive:
1. Cut open the cable screen in the middle of the stripped area (1 in Fig. 6-28).
2. Pull the cable screen ends over the cable insulation to turn the conductive side
inside out (2 in Fig. 6-28).
3. Connect the screens ends with a continuous conducting foil (3 in Fig. 6-28).
Figure 6-28 Preparing the screens of control cables for EMC plates
1) Cable screen
2) Cable screen ends
3) Conductive foil
2