MECHANICAL INSTALLATION
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
91/266
5.6. Joining water pipes
The pipe joints of two adjoining transport units have been slid onto the water
pipes in the factory. The locking bolts show into the direction where they can be
reached best with a wrench.
1. Mark the length of a pipe joint on one end of a water pipe as a fitting guide.
2. Slide the pipe joint over the two adjoining pipe ends.
3. Center the pipe joint.
4. Orientate the locking bolts of the pipe joint for the return water pipes
(Fig. 5-2).
WARNING! Flashover hazard! The locking bolts maintain the required minimum
distances between pipe joint and busbars to prevent flashover when the drive
is energized.
Figure 5-2 Minimum distances and locking bolt orientation (A = front)
1) 40 mm minimum 2) Locking bolt orientation
1
2
2
3