COMMISSIONING
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
159/266
7) Wiring across shipping splits is completed according to the instructions
in this user manual (3BHS212794 E01 N).
8) Ground cable of the drive is securely connected at both ends.
9) Cable armor and screens of power supply cables are connected to PE
ground busbar.
10) The transformer and motor cables are installed but the conductors not
connected at both ends (cables and drive must be insulation resistance
tested, ie, Megger test, before connection).
7.6.3. Main circuit breaker (MCB)
1) MCB selected as per Main circuit breaker specification
(1)
2) High-voltage power connections completed
3) MCB is ready to be tested with drive
4) MCB protection relay settings are tested
5) Protection devices (eg, door locks) are tested and in operation.
6) Local operation of MCB is disabled.
7) Emergency-off loop is tested.
(1)
Pay attention to MCB opening time and installation of undervoltage coil or second
opening coil
7.6.4. Input transformer checklist
1) Grounding is completed
2) Transformer auxiliaries (eg, dehydrating breathers, cooling, protection
devices) are ready.
3) Protection devices are tested and in operation.
7.6.2. Electrical installation checklist (continued)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS6080 and is the answer not in the manual?

ABB ACS6080 Specifications

General IconGeneral
BrandABB
ModelACS6080
CategoryDC Drives
LanguageEnglish

Related product manuals