Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 97
BMS Configuration
Select BMS Config to configure building management protocol settings (BACnet,
Modbus). By default neither protocol is enabled.
Table 45: BMS configuration options
Option
Description Default value
Protoc
Configures the BMS protocol (NO, BACnet, or
Modbus)
NO
InitPan [1]
Configures the initial panel address when using
Modbus in Zonepoint mode
001
Mode [1]
Configures the Modbus mode (Zonepoint or Zone) Zonepoint
[1] Not applicable for BACnet.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select BMS Config.
3. Configure all required settings.
Initpan is only required when using Modbus in Zonepoint mode.
Zonepoint mode implements Modbus services for 32 networked fire panels
with consecutive addresses (for example, 1 to 32 if the address of the first
panel is defined as 001 in InitPan).
Zone mode implements Modbus services for 128 networked fire panels
(InitPan is not required).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Table of Contents

Other manuals for Aritech 2X-AF2-FB-PRT-P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-AF2-FB-PRT-P and is the answer not in the manual?

Aritech 2X-AF2-FB-PRT-P Specifications

General IconGeneral
BrandAritech
Model2X-AF2-FB-PRT-P
CategorySmoke Alarm
LanguageEnglish

Related product manuals