Chapter 3: Configuration and commissioning
126 2X-A Series Installation Manual
Loop Class configuration
Select Loop Class to configure the installation loop Class (Class A or Class B).
The default setting is Class A.
To configure a loop as Class A or Class B:
1. Select Field setup in Main menu.
2. Select Loop Class and select the loop number (1 for one-loop panel; 1 or 2 for
two-loop panel, etc.).
3. Select Class A or Class B.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
High-Power Loop configuration
Select High-Power Loop to configure a high-power loop (increase the maximum
loop output from 500 mA to 800 mA). The default setting is NO.
Note: This option requires the 2010-2A-PAK-HPL (not supplied).
To configure a high-power loop:
1. Select Field setup in Main menu.
2. Select High-Power Loop.
3. Select Enable, and then select YES (to enable a high-power loop) or NO (to
disable a high-power loop).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.