Chapter 1: Introduction
2X-A Series Installation Manual 15
Conditions
A summary of system events logged as conditions is shown below.
Table 9: System events logged as conditions
Description
A device is in alarm but the system is waiting for an
additional alarm event to confirm the zone alarm
Configuration device connected
A control panel configuration session is initiated via an
external device (PC, laptop, etc.)
The system started but the date and time are not set
The default Operator, Maintenance, or Installer password
should be changed.
A control panel feature or device is disabled
The control panel event log is full
Extinguishing is blocked, disabled, or has a fault
Extinguishing I/O device [1]
An extinguishing I/O device is active, being tested, is
disabled, or has a fault
Incompatible firmware version
An expansion board (for example, a loop board, a network
board, or DACT board) has an incompatible firmware
version. The control panel firmware version should be
updated.
An input is activated (subject to configuration)
Loop device not configured
A loop device is detected that is not configured
Loop manual fast compensation
Fast sensitivity compensation is active for a loop
A loop power status is OFF
Maximum conventional zones
exceeded in a network
The number of conventional zones in a fire network
exceeds the maximum allowed
Maximum loops exceeded in a
network
The number of loops in a fire network exceeds the
maximum allowed
New node in the fire network
A control panel has been added to the fire network
An output group is activated
A device (and corresponding zone) is in prealarm
routing, and fire
A sounder, fire routing, or fire protection delay is enabled or
disabled
A control panel feature or device is being tested
[1] These condition types only apply if an extinguishing panel is included in the fire network.