Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 63
The Reports menu
Use the Reports menu to view, clear, or back up the event log and to display a
variety of system status reports. The reports available to maintenance users are
shown in the table below.
Table 24: Reports available to maintenance users
Report
Description
Event log
Displays, clears, or backs up the event log. The event log contains all
the alarm, fault, and condition events recorded by the control panel.
Attention required
Displays all devices reporting a fault condition.
Revision
Displays your control panel software revision, control panel
configuration revision, and system boards serial number data.
Contact details
Displays maintenance or installation contractor contact information
(subject to installer configuration).
Zone status [1]
Displays the current status information for zones.
Zone mapping [1]
Displays which devices are assigned to each zone in your fire system.
Device status [1]
[2] Displays the current status information for control panel devices.
Device information available in real time includes: instant, mean,
maximum, and minimum analog values, alarm level, communication
error rate, and the loop input contamination level.
Panel I/O status
Displays t
he current status information for the control panel inputs and
outputs.
Output Groups status [1]
Displays the control panel output groups (sounders, fire routing, fire
protection, or program) that are currently active.
Rules status
Displays the control panel rules that are currently active. A rule
consists of one or more states (combined by Boolean operators) that
are configured to trigger specific system actions after a specific
confirmation time. Rules are created using the Configuration Utility.
Firenet status
Displays the current status for all control panels in the fire network.
Save/Print reports
Saves or prints reports.
PAK List
Displays details of all PAKs currently registered to the control panel.
[1] These reports are
not available for repeater panels.
[2] At installer level, this report screen also includes the option to perform fast
sensitivity
compensation for detectors.

Table of Contents

Other manuals for Aritech 2X-AF2-FB-PRT-P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-AF2-FB-PRT-P and is the answer not in the manual?

Aritech 2X-AF2-FB-PRT-P Specifications

General IconGeneral
BrandAritech
Model2X-AF2-FB-PRT-P
CategorySmoke Alarm
LanguageEnglish

Related product manuals