28 2X-A Series Installation Manual
Battery installation
Compatible batteries
The control panel requires two 12 V, rechargeable, sealed lead-acid batteries.
Use only the compatible batteries shown below.
Caution: Not all compatible batteries can be used with all control panels. Some
compatible batteries must be installed in an external battery box (not supplied).
See “Installing batterieson page 30 for more information.
Table 11: Compatible batteries
Type
Make and model 4 A PSU 6 A PSU 10 A PSU [1]
12 V, 7.2 Ah
Aritech BS127N-A X X
MultiPower MP7.2-12 X X
Fiamm FG20721/2 X X
Yuasa NP7-12 X X
Power Sonic PS-1270
12 V, 12 Ah
Aritech BS130N X X
Fiamm FG21201/2 X X
Yuasa NP12-12 X X
Power Sonic PS-12120 X
12 V, 17/18 Ah
Aritech BS131N X X
Fiamm FG21703 X X
Yuasa NP17-12 X X
Power Sonic PS-12170VDS X
12 V, 36/38 Ah
Aritech BS134N X
Yuasa NP38-12I X
Power Sonic PS-12380VDS X
12 V, 65 Ah
Aritech BS133N X
Yuasa NP65-12I X
Power Sonic PS-12650VDS X
[1] Control
panels with a 10 A PSU require the battery type to be configured see “Battery type
configurationon page 29.

Table of Contents

Other manuals for Aritech 2X-AF2-FB-PRT-P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-AF2-FB-PRT-P and is the answer not in the manual?

Aritech 2X-AF2-FB-PRT-P Specifications

General IconGeneral
BrandAritech
Model2X-AF2-FB-PRT-P
CategorySmoke Alarm
LanguageEnglish

Related product manuals