Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 79
Other settings
24V auxiliary
Select 24V AUX config to configure the 24V AUX output state during reset and
when the control panel is running on battery power. The default setting for both
options is NO (the 24V AUX output is not deactivated).
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select 24V AUX config.
3. Select YES or NO for deactivation during reset.
4. Select YES or NO for deactivation when running on battery power.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Fault notification
Select Fault notification to configure the reporting status for selected faults
(shown below). The default setting for fault notifications is YES (all faults are
reported).
Table 31: Fault notification settings
Description
Configures battery fault reporting
Configures earth fault reporting
Configures external power supply low voltage fault reporting
available for fire alarm control panels and repeaters
[2] This option is only available for compact repeaters
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Fault notification.
3. For each notification type, select YES to enable notifications or NO to disable
notifications.
If NO is selected, the corresponding faults are not recorded in the event log.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.