Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 51
Maintenance level operation and
configuration
The maintenance level is password-protected and is reserved for authorized
users trained to operate the control panel and perform routine maintenance tasks
for the fire system. The default password for the default maintenance user is
3333.
The maintenance level lets you:
Perform all operator level tasks described in the operation manual
Change the control panel time and date and synchronize the time and date in
a fire network
Change the day/night mode time and holiday calendar settings (fire alarm
control panels only)
Change the TCP/IP, email, and USB communications settings
Back up or clear the event log
View and save reports
Disable or enable system features or loop devices
Test zones, inputs, outputs (including output groups), and batteries
Change the user passwords
Locate devices
Activate service mode for testing purposes
The Main menu
The maintenance level Main menu is shown below.
Figure 22: Maintenance level Main menu

Table of Contents

Other manuals for Aritech 2X-AF2-FB-PRT-P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-AF2-FB-PRT-P and is the answer not in the manual?

Aritech 2X-AF2-FB-PRT-P Specifications

General IconGeneral
BrandAritech
Model2X-AF2-FB-PRT-P
CategorySmoke Alarm
LanguageEnglish

Related product manuals