Chapter 5: Technical specifications
140 2X-A Series Installation Manual
[4]
4 A power supply
Two-loop control panel with 24-zone
indicator board, network board, and
DACT board installed.
6 A power supply
Four-loop control panel with internal
printer, loop board, 40-zone indicator
board, network board, DACT board,
and peripherals interface board
installed.
10 A power supply
Four-loop control panel with internal
printer, loop board, 40-zone indicator
board, network board, DACT board,
and peripherals interface board
installed.
400 mA at 24 VDC
600 mA at 24 VDC
600 mA at 27.6 VDC
[2] Imax. a is the rated maximum output current which can be supplied continuously.
[3] Imax. b is the rated maximum output current which can be
supplied for a short duration in
which battery charging is not required.
For other control panel configurations, use the NeXT System Builder application to calculate
Battery and battery charger specifications
For recommended battery specifications, see “Compatible batteries” on page 28.
Sealed lead-acid batteries (2X)
27.3 V at 20ºC – 36 mV/ºC
4 A power supply
6 A power supply
10 A power supply
1.2 A max.
1.2 A max.
2.8 A max.
23.6 VDC ± 1% at 25ºC
Note: Additional 0.2 V (max.) drop if Imax b current in battery
cables.
21.5 VDC ± 1% at 25ºC
System shutdown (for battery
protection)
21 VDC ± 1% at 25ºC
internal resistance
Ri max.)
0.5 Ω