your site configuration before installation. After installation, make sure the site maintains the environmental
characteristics, as shown in the below table.
Table 11: Cisco ASR 1001-X Router Environmental Tolerance
MaximumMinimumEnvironmental Characteristic
40° C
(40° C up to 10,000 feet)
0° COperating temperature (nominal)
50° C0° COperating temperature (short term)
+70° C
–20° C
Storage temperature
90%10%Operative humidity (nominal)
(relative humidity)
90%5%Operative humidity (short term)
95%5%Storage humidity (relative
humidity)
10,000 feet
–500 feet
Altitude, operating: over allowable
temperature range (0 to 50 degrees
C)
50,000 feet
–1000 feet
Altitude, nonoperating: over
allowable temperature range
+70° C
–25° C
Thermal shock nonoperating with
change over time of 3 minutes
+50° C0° CThermal Shock - Operating at 2.5
degree C per minute
Physical Characteristics
Be familiar with the physical characteristics of the Cisco ASR 1001-X Router to assist you in placing the
system at a proper location.
For information regarding rack widths supported for the Cisco ASR 1001-X Router, see the following sections:
The below table shows the weight and dimensions of the Cisco ASR 1001-X Routers.
Table 12: Physical Characteristics of Cisco ASR 1001-X Router
Cisco ASR 1001-XCharacteristic
1.71 in. (43.43 mm) —1RU; rack-mount per EIA
RS-310
Height
Cisco ASR 1001-X Router Hardware Installation Guide
32
Preparing Your Site for Installation
Site Selection Guidelines