Power [kW (hp)
SIBA Type RK1
Littelfuse Type RK1
Ferraz Shawmut Type RK1
Ferraz Shawmut J
30 (40)
5014006-063
KLS-R-060
A6K-60-R
HSJ-60
37 (50)
5014006-080
KLS-R-075
A6K-80-R
HSJ-80
45 (60)
5014006-100
KLS-R-100
A6K-100-R
HSJ-100
55 (75)
2028220-125
KLS-R-125
A6K-125-R
HSJ-125
75 (100)
2028220-150
KLS-R-150
A6K-150-R
HSJ-150
90 (125)
2028220-200
KLS-R-175
A6K-175-R
HSJ-175
Table 82: Recommended Maximum Fuse, 525–690 V, Enclosure Sizes A, B, and C
Power
[kW (hp)]
Maxi-
mum
Prefuse
size [A]
Bussmann
E52273
RK1/JDDZ
Bussmann
E4273 J/
JDDZ
Buss-
mann
E4273 T/
JDDZ
SIBA E180276
RK1/JDDZ
Littelfuse
E81895
RK1/JDDZ
Ferraz- Shaw-
mut E163267/
E2137 RK1/
JDDZ
Ferraz-
Shawmut
E2137
J/HSJ
11–15
(15–20)
30
KTS-R-30
JKS-30
JJS-30
5017906-030
KLS-R-030
A6K-30-R
HST-30
22 (30)
45
KTS-R-45
JKS-45
JJS-45
5014006-050
KLS-R-045
A6K-45-R
HST-45
30 (40)
60
KTS-R-60
JKS-60
JJS-60
5014006-063
KLS-R-060
A6K-60-R
HST-60
37 (50)
80
KTS-R-80
JKS-80
JJS-80
5014006-080
KLS-R-075
A6K-80-R
HST-80
45 (60)
90
KTS-R-90
JKS-90
JJS-90
5014006-100
KLS-R-090
A6K-90-R
HST-90
55 (75)
100
KTS-R-100
JKS-100
JJS-100
5014006-100
KLS-R-100
A6K-100-R
HST-100
75 (100)
125
KTS-R-125
JKS-125
JJS-125
2028220-125
KLS-150
A6K-125-R
HST-125
90 (125)
150
KTS-R-150
JKS-150
JJS-150
2028220-150
KLS-175
A6K-150-R
HST-150
Table 83: Recommended Maximum Fuse, 525–690 V, Enclosure Sizes B, and C
Power
[kW (hp)]
Maxi-
mu m
prefuse
[A]
Bussmann
E52273
RK1/JDDZ
Bussmann
E4273 J/
JDDZ
Buss-
mann
E4273 T/
JDDZ
SIBA E180276
RK1/JDDZ
Littelfuse
E81895
RK1/JDDZ
Ferraz Shaw-
mut E163267/
E2137 RK1/
JDDZ
Ferraz
Shawmut
E2137
J/HSJ
11–15
(15–20)
30
KTS-R-30
JKS-30
JKJS-30
5017906-030
KLS-R-030
A6K-30-R
HST-30
18.5 (25.0)
45
KTS-R-45
JKS-45
JJS-45
5014006-050
KLS-R-045
A6K-45-R
HST-45
30 (40)
60
KTS-R-60
JKS-60
JJS-60
5014006-063
KLS-R-060
A6K-60-R
HST-60
37 (50)
80
KTS-R-80
JKS-80
JJS-80
5014006-080
KLS-R-075
A6K-80-R
HST-80
45 (60)
90
KTS-R-90
JKS-90
JJS-90
5014006-100
KLS-R-090
A6K-90-R
HST-90
55 (75)
100
KTS-R-100
JKS-100
JJS-100
5014006-100
KLS-R-100
A6K-100-R
HST-100
75 (100)
125
KTS-R-125
JKS-125
JJS-125
2028220-125
KLS-150
A6K-125-R
HST-125
90 (125)
150
KTS-R-150
JKS-150
JJS-150
2028220-150
KLS-175
A6K-150-R
HST-150
10.7 Relays
Relay 1
AJ300847815559en-000101 / 130R0337134 | Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide

Table of Contents

Other manuals for Danfoss VLT AQUA FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA FC 202 and is the answer not in the manual?

Danfoss VLT AQUA FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals