Displacement power factor (cos Φ)
Near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups) ≤7.5 kW
Maximum 2 times per minute
Switching on input supply L1, L2, L3 (power-ups) 11–90 kW
Maximum 1 time per minute
Environment according to EN60664-1
Overvoltage category III/pollution degree 2
1
Mains voltage low/mains drop-out: During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be exptec-
ted at mains voltage lower than 10% below the drive's lowest rated supply voltage.
2
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/500/600/690 V maximum.
3
The drive power supply is tested in accordance with IEC 61000-4-28, 50 Hz +4/-6%.
8.3 Motor Output and Motor Data
8.3.1 Motor Output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–590 Hz
(1)
Switching on output
Unlimited
Ramp times
1–3600 s
1
Dependent on power size.
8.3.2 Torque Characteristics, Normal Overload
Starting torque (constant torque)
Maximum 110% for 60 s, once in 10 minutes
(1)
Overload torque (constant torque)
Maximum 110% for 60 s, once in 10 minutes
(1)
1
Percentage relates to the nominal torque of the drive, dependent on power size.
8.3.3 Torque Characteristics, High Overload
Starting torque (constant torque)
Maximum 150/160% for 60 s, once in 10 minutes
(1)
Overload torque (constant torque)
Maximum 150/160% for 60 s, once in 10 minutes
(1)
1
Percentage relates to the nominal torque of the drive, dependent on power size.
8.4 Ambient Conditions
8.4.1 Environment
Enclosure size A
IP20/Chassis, IP21/Type 1, IP55/Type 12, IP66/Type 4X
Enclosure sizes B1/B2
IP21/Type 1, IP55/Type 12, IP66/Type 4X
Enclosure sizes B3/B4
IP20/Chassis
Enclosure sizes C1/C2
IP21/Type 1, IP55/Type 12, IP66/Type 4X
Enclosure sizes C3/C4
IP20/Chassis
Enclosure kit available ≤ enclosure size A
IP21/TYPE 1/IP4X top
Vibration test enclosure A/B/C
1.0 g
Maximum relative humidty
5–95% (IEC 721-3-3); Class 3K3 (non-condensing) during opera-
tion
Aggressive environment (IEC 60068-2-43), uncoated
Class 3C2
Aggressive environment (IEC 60068-2-43), coated
Class 3C3
Test method according to IEC 60068-2-43
H2S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating
Maximum 55° C (131° F)
(1)
AJ300847815559en-000101 / 130R033790 | Danfoss A/S © 2020.09
Specications
VLT® AQUA Drive FC 202
Design Guide

Table of Contents

Other manuals for Danfoss VLT AQUA FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA FC 202 and is the answer not in the manual?

Danfoss VLT AQUA FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals