4.5.2 Ground
The diameter of the ground should not be less than
the diameters of the cables connected to the
terminals L and N.
If using multiple pieces of equipment, use a
single-point ground.
AS S eries
Power Module
or
AS100 P LC CPU
Another piece of
equipment
The single-point ground is better.
If you cannot use a single-point ground, use a
common-point ground.
AS Series
Power Module
or
AS100 PLC CPU
The comm on-point ground is permitted.
Another piece o f
equipment
Do not connect equipment ground wires together
as shown on the right.
AS Series
Power Module
or
AS100 PLC CPU
The equipment can not be grounded in this way.
Another piece o f
equipment
4.5.3 Wiring Power Supply
AS200 / AS300 PLC CPU
AS-PS02
LG
L
N
PS02 AS Series
Control Box
100~240V