X0.0
T2
Y0.0
SV: K100
T1+T2=10sec
T250(PV)
T1
C. Timer used in the function block
Use the T412–T511 timers for the function block or the interrupt.
When the instruction TMR or END is executed, the timer used in the functional block begins to count.
When the value of the timer matches the timer setting value, the output coil is ON.
If you use the general-purpose timer is used in the function block or the interrupt, and the functional or
interrupt is not executed, the timer cannot count correctly.
5.2.10 16-bit Counters
Characteristics of the 16-bit counter
Item 16-bit counter
Type General type
Number C0–C511
Direction Counting up
Setting value 0–32,767
Specificying the counter setting
value
The setting value can be either the constant or the value in the data
register.
Change of the current value
The counter stops counting when the value of the counter matches the
setting value.
Output contact The contact is ON when the value of the counter matches the setting value.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS132P-A and is the answer not in the manual?

Delta AS132P-A Specifications

General IconGeneral
BrandDelta
ModelAS132P-A
CategoryNetwork Hardware
LanguageEnglish

Related product manuals