4.6 Wiring CPU Modules
When you use open collector NPN/PNP outputs to activate AS300 high speed inputs, you need to
have the pull up/pull down resistor connected to X point and S/S. Only use 3 W / 470 ohm or 2 W / 1
Kohm resistors.
When you use Push-Pull outputs to activate AS PLC CPU high speed inputs, you don’t need to use
any pull up/pull down resistor connected to X point and S/S.
While using ports Y as output ports, all the C0 points should be connected. Do NOT only use ONE C0
point.
Note:
In case open collector NPN/PNP outputs are used to activate AS300 high speed inputs, you need to
have the pull up/pull down resistor connected to X point and S/S.
In case Push-Pull outputs are used to activate AS300 high speed inputs, you don’t need to use any
pull up/pull down resistor connected to X point and S/S.
It is recommended to use the resistor of 3W/470ohm or 2W/1Kohm.
While using ports Y as output ports, all the C0 points should be connected. Do NOT only use ONE C0
point.
Through the following wiring you can increase the resistance of a resistor. See the illustration below for
reference.
NPN PNP
S/S
X
24V
0V
R
S/S
X
R
0V
24V
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS132P-A and is the answer not in the manual?

Delta AS132P-A Specifications

General IconGeneral
BrandDelta
ModelAS132P-A
CategoryNetwork Hardware
LanguageEnglish

Related product manuals