12.3.6
Troubleshooting for the Module AS00SCM as a Communication
Module
12.3.6.1 ERROR LED Indicators Are ON
The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU
module and acts as a communication module.
Error
Code
Description Solution
16#1605 Hardware failure
1. Check that the module is securely installed.
2. Install a new AS00SCM or if the problem persists,
contact the local authorized distributors.
16#1606 The function card setting is incorrect.
1. Check if the function card is securely installed.
2. Install a new function card or if the problem persists,
contact the local authorized distributors.
3. Check if the setting in HWCONFIG is consistent with
the function card setting.
4. Install a new AS00SCM or if the problem persists,
contact the local authorized distributors.
12.3.6.2 ERROR LED Indicators Blinking Every 0.5 Seconds
The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU
module and acts as a communication module.
Error
Code
Description Solution
16#1802 Incorrect parameters
Check the parameter in HWCONFIG. Download the
parameter again.
16#1803 Communication timeout
1. Check whether the communication cable is
properly connected.
2. Check if the station number and the
communication format are correctly set.
3. Check if the connection with the function card is
working correctly.
16#1804 The UD Link setting is incorrect.
1. Check the settings of the UD Link.
2. Check the warning settings in the PLC.
The following error codes can only be viewed with SCMSoft; when the following errors occur, they are not shown on the
LED indicators and the system does not send the error messages to the CPU module.
Error
Code
Description Solution
16#0107
The settings in HWCONFIG and manual
settings are not consistent with function
card 1.
Check the settings in HWCONFIG and manual
settings for function card 1.
16#0108
The settings in HWCONFIG and manual
settings are not consistent for function card
2.
Check the settings in HWCONFIG and manual
settings for function card 2.
16#0201 Incorrect parameters
Check the parameter in HWCONFIG. Download the
parameter again.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS132P-A and is the answer not in the manual?

Delta AS132P-A Specifications

General IconGeneral
BrandDelta
ModelAS132P-A
CategoryNetwork Hardware
LanguageEnglish

Related product manuals