13.3.4 Steps to Restore Delta Device Parameters
Two ways you can use to restore the Delta device parameters. One is to use ISPSoft to perform the restoration and the
other way is to send commands (SM/SR) to the SD card of the AS Series PLC CPU through HMI. Refer to section
3.1.4.16 Delta Device Parameters Backup and Restore from ISPSoft User Manual for more information. Here we focus on
the operation of sending commands (SM/SR) to the SD card of the AS Series PLC CPU through HMI.
Use SM/SR devices to appoint which Delta drive should be restored. Refer to the table below. After you have set the
configurations, the PLC executes the restorations when the PLC is Power-On or from Stop to Run.
SM / SR Function Description Retainable
SR1600 Parameter restoration code
0: No action (default)
1: The AS Series PLC CPU executes the
restoration when the PLC is Power-On or from Stop
to Run. When the restoration is complete, reset the
value to 0.
Yes
SR1601.0
~
SR1601.15
and
SR1602.0
~
SR1602.15
Target device number to perform
parameter restoration
SR1601.0: corresponding to target device #1
SR1601.1: corresponding to target device #2
SR1601.15: corresponding to target device #16
OFF: No action (default)
ON: Execute restoration on the appointed target
device.
Yes
SR1603
The total number of Delta drives that
error has occurred during restoration
0: No error occurred
1~16: The total number of Delta drives that error
has occurred during restoration
No
SR1604
The last digit of the device’s IP
address that a most recent error
occurred during restoration
0 ~ 255: The last digit of the device’s IP address
that a most recent error occurred during restoration.
(Only valid when SM1161 is switched to ON. Find
SM1161 description below.)
No
SR1605
The error code of the last device that
error occurred
Refer to the error code table below. No
SM1160 Parameter restoration complete
OFF: When the value in SR1600 changes from 1 to
0, reset SM1160 to OFF.
ON: When the restoration is complete and
successful, SM1160 switches to ON.
No
SM1161
Error occurred during parameter
restoration
OFF: When the value in SR1600 changes from 1 to
0, reset SM1160 to OFF.
ON: If any error occurred during restoration,
SM1161 switches to ON.
No
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com