The control message format for the node state:
0 Command specifier (CS)
Slave address
(0: Broadcast)
The command specifiers:
Command specifier
Function
Enter the pre-operational state
Reset the application layer
82 Reset the communication
Error control services
The error control service detects the disconnection of a network node. The error control services are
classified into two types: Heartbeat and Node Guarding. The AS Series PLC only supports Heartbeat.
For example, the master can detect the disconnection of the slave only after the slave enables the
Heartbeat service.
The following illustrates the Heartbeat principle. The Heartbeat producer transmits the Heartbeat
message according to the set Heartbeat producing time. One or many Heartbeat consumers detect the
message transmitted by the Heartbeat producer. If the consumer does not receive the message
transmitted by the producer within the timeout period, there is a problem in the CANopen
communication or the producer is disconnected.
producing
time
timeout
period
timeout
period