Error
Code
(16#)
Description Solution Flag Log
not used properly.
0E05
The operands HCXXX used in
DCNT are not used properly.
SM5 X
1000
-
10FF
System error
If the problem persists, contact the local authorized
distributors.
- V
1300
-
130F
Errors occurred in the remote
modules
Refer to Section 12.3.7 for more information on the error
codes for the remote modules.
SM30
V
1402
The arrangement of the I/O
modules is not consistent with the
settings.
Check whether the settings in HWCONFIG are
consistent with the arrangement of the I/O modules.
SM10
V
140B
The number of connected
communication modules exceed the
maximum number 4.
Check the total number of communication modules. SM10
V
140C
The number of connected
positioning modules exceed the
maximum number 8.
Check the total number of positioning modules. SM10
V
140D
The number of connected extension
modules exceed the maximum
number 32.
Check the total number of extension modules. SM10
V
140E
More than eight remote modules on
the right side of the CPU module.
Check the total number of remote modules on the right
side of the CPU module (maximum is 8).
SM30
V
1600
The extension module ID exceeds
the range.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the problem persists, contact the local authorized
distributors.
SM10
V
1601
The extension module ID cannot be
set.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the problem persists, contact the local authorized
distributors.
SM10
V
1602
The extension module ID is
duplicated.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the problem persists, contact the local authorized
distributors.
SM10
V
1603
The extension module cannot be
operated.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the problem persists, contact the local authorized
distributors.
SM10
V
1604
Extension module communication
timeout
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the problem persists, contact the local authorized
distributors.
SM10
V
1605 Hardware failure
If the problem persists, contact the local authorized
distributors.
SM10
V
1606
Errors on the communication
module function card
Make sure the function card is properly connected to the
CPU module and turn the modules on again.
SM10
V
1607 The external voltage is abnormal.
Check whether the external 24 V power supply to the
SM10
V
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com