ADV200 • Functions description and parameters list 11
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.13 292 Sensor inp X mon degC FLOAT 16 0.0 0.0 0.0 ER FVS
Display of temperature in degrees centigrade measured by KTY84 sensor connected to dedicated input of
EXP-IO-SENS-100-ADV and EXP-IO-SENS-1000-ADV expansion cards.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.14 1544 An inp 1 temp mon degC FLOAT 16 0.0 0.0 0.0 ER FVS
1.15 1594 An inp 2 temp mon degC FLOAT 16 0.0 0.0 0.0 ER FVS
Display of temperature in degrees centigrade measured by KTY84 sensor connected to analog input 1 or 2 of
control board.
These parameters are on the L_TEMPCTRL selection list and can be assigned as selection to source param-
eter 6040 Liquid temp src.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.16 1610 An inp 1X temp mon degC FLOAT 16 0.0 0.0 0.0 ER FVS
1.17 1660 An inp 2X temp mon degC FLOAT 16 0.0 0.0 0.0 ER FVS
Displays temperature in °C with PT100/PT1000/NI1000 from input 1 (PAR 1610) or input 2 (PAR 1660) of EXP-
IO-SENS-100-ADV or EXP-IO-SENS-1000-ADV card, regardless of how the motor overtemperature alarm is
managed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.18 2342 Working load perc FLOAT 0.0 0.0 0.0 ER F_S
Normal motor torque scaled according to setting of parameter Torque scale factor IPA 2340. This value is
expressed in %.
This parameter is obtained with the following formula:
Scaled torque % = Torque % (IPA 2394) * 100 / Torque scale factor.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.19 280 Torque current ref A FLOAT 16/32 0.0 0.0 0.0 ER F_S
The current reference used for torque control is displayed (in the Flux vector OL and Flux vector CL
modes
).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.20 282 Magnet current ref A FLOAT 16/32 0.0 0.0 0.0 ER F_S
The magnetizing current reference is displayed
(in the Flux vector OL and Flux vector CL
modes
).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.21 284 Torque current A FLOAT 16/32 0.0 0.0 0.0 ER FVS
The actual torque current value is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.22 286 Magnet current A FLOAT 16/32 0.0 0.0 0.0 ER FVS
The actual magnetizing current value is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.23 3212 Motor overload accum perc UINT16 16/32 0 0 100 ER FVS
The motor overload level is displayed (100% = alarm threshold).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.24 368 Drive overload accum perc UINT16 16/32 0 0 100 ER FVS
The drive overload level is displayed. An instantaneous overload of 180% of the drive rated current is allowed
for 3 s. The thermal image I²t adjusts the drive output current thresholds. During normal operation, the instan-
taneous output current value can reach 180% of the drive rated current. After 0,5 s at 180%, the output current

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals