Specifications
This section contains specifications for the models S80 and S85 system. The system
rack, I/O rack, and the I/O drawers each have separate sections.
Models S80 and S85 System Rack
The mechanical packaging, cooling, power supply, and environmental requirements for
the system rack are shown in the following table:
Dimensions
Height
Width
Depth
1577 mm
567 mm
1041 mm
62.0 in.
22.3 in.
40.9 in.
Weight
Minimum
(Configuration dependent)
400 kg 880 lbs.
Electrical
Power source loading
(maximum in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output (maximum)
Power requirements (maximum)
Power factor
Inrush current³
Maximum altitude
2.129KVA
200 to 240
50-60
6904 BTU/hr
2023 watts
0.92 to 0.98
43 amps
2135 m (7000 ft.)
Temperature Range
4,5,6
Operating
10 to 37.8°C
(50to100°F)
Non-Operating
1to60°C
(34to140°F)
Humidity (Noncondensing)
Wet Bulb Requirements⁵
Operating
8to80%
23°C(73°F)
Non-Operating
8to80%
23°C(73°F)
Noise Emissions
1,2
L
WAd
L
pAm
<L
pA
>
m
Impulsive or prominent
discrete tones
Operating
7.0 bels
N/A
N/A
No
Idle
7.0 bels
N/A
N/A
No
Clearances
Install/Air Flow
Service
Maintenance of a proper service clearance should allow proper air flow.
See “System Service Clearances” on page 70.
Chapter 1. Reference Information
67