6
1
KEB COMBIVERT F5-M / S28
Name: Basis
12.05.04
Chapter Section Page Date
© KEB Antriebstechnik, 2002
All Rights reserved
Functional Desription Operating and Unit Data
Adr.
min max
default
0035h
1
rpm
0
32000-32000
Sy. 53 Actual speed value
With this parameter the current actual speed can be readout in rpm. The direction of rotation is signaled by the sign.
Adr.
min max
default
0038h
1
hex
0203
7FFFh0
Sy. 56 Start display address
Sy.56 adjusts the parameter address which shall be represented on switching on the operator. Only valid addresses are
accepted.
If this parameters is available in the CP-Mode, the setting becomes effective there. Otherwise CP.0 is indicated as start
parameter.
Adr.
min max
default
0034h
1
rpm
0
32000-32000
Sy. 52 Set speed value
Presetting of the setpoint speed in the range of ±16000 rpm. The source of direction of rotation is determined as with the
other absolute setpoint sources over oP.1. The setpoint source oP.0 must be adjusted to Ñ5ì for setpoint setting by Sy.52.