147
Input/Output Con guration
9.2 Digital Output
Parameters
The digital output parameters can be used to con gure the digital
outputs for operation. Normally these parameters only need to be
adjusted by the Elevator control builder.
do.42
Output
Inversion
Can be used to invert the function of the output. As an example, normally on becomes
normally off. Each output is assigned a value. To invert the output set this parameter
to the corresponding value. To invert more than one output set this parameter to
the sum of the values. Example X2A.18 = 1 and X2A.19 = 2, to invert both set this
parameter equal to 3.
Value Output Terminal
1 X2A.18 +24VDC solid state output
2 X2A.19 +24VDC solid state output
4 X2A.24..26 form C relay output
8 X2A.27..29 form C relay output
Unit: -
Value Range: 0...15
Default Setting: 0
This parameter determines the function of the +24VDC solid state drive output
X2A.18. The function can be selected from the table on the following page.
Default Setting: ASd
This parameter determines the function of the +24VDC solid state drive output
X2A.19. The function can be selected from the table on the following page.
Default Setting: FLt
This parameter determines the function of the relay output X2A.24..26. The function
can be selected from the table on the following page.
Default Setting: rdy
This parameter determines the function of the relay output X2A.27..29. The function
can be selected from the table on the following page.
Default Setting: dro
do.80
Output
X2A.18
do.81
Output
X2A.19
do.82
Output
X2A.24..26
do.83
Output
X2A.27..29