Model 6220/6221 Reference Manual DC Current Source Operation 3-13
Return to Section 3 topics
Autorange
Front panel operation
The AUTO range key is a single action control to select the best fixed range for the
displayed source value. After setting a source value, pressing AUTO will ensure
that the best fixed range is selected.
For example, assume the source is set to +1mA on the 20mA range (+01.000mA
displayed). When the AUTO key is pressed, the range will change to the 2mA
range (which is the best range).
Autorange is only asserted (enabled) for the instant that the AUTO key is pressed.
Therefore, the AUTO annunciator does not turn on. If already on the best range,
pressing AUTO will have no action.
Remote operation
For remote operation, autorange remains active when it is enabled. When the
source value is changed, the range will (if needed) automatically change to the
best range for that value. With auto range enabled, the AUTO annunciator turns
on to indicate that autorange is active.
For example, assume autorange is enabled, and the source is presently set for
1mA on the 1mA range. When the source value is changed to 5mA, the range will
automatically uprange to the 10mA range.
Active autorange will disable if a command to select a fixed range is sent. The
commands to control autorange and select a fixed range are listed in Tabl e 3- 2 .
Source preset
The PRES key can be used to set the source to a preset value and range. When
the PRES key is pressed, the source will select the preset range set the preset
value. The preset value is set as follows:
1. Press the PRES key. The message “PRES” is displayed while the preset
value is being used.
2. Using the source editing keys as explained in Figure 3-3 and Figure 3-4, set
the preset value to the desired level.
NOTE Active autorange is only intended for remote opera-
tion. When the Model 622x is taken out of remote (e.g.,
LOCAL key pressed), the AUTO annunciator stays on
and automatic down-ranging remains active. Active
autorange will disable (AUTO annunciator turns off)
when a RANGE or
key is pressed.
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Keithley 6220 and is the answer not in the manual?

Keithley 6220 Specifications

General IconGeneral
BrandKeithley
Model6220
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals