Wiring the standard device
Basic devices in the power range 15 ... 30 kW
Motor connection
5
5.5
5.5.4
5.5-9
EDSVF9333V EN 3.0-06/2005
Features of the connection for motor temperature monitoring:
Pin X8/5, X8/8 from incremental encoder input (X8)
Connection Linear KTY thermal sensor
Tripping point z Warning: Adjustable
z Error (TRIP): Fixed at 150 °C
Notes z Monitoring is not active in the Lenze setting.
z The KTY thermal sensor is monitored with regard to interruption
and short circuit.
PE
T1
T2
U
VW
2
3
}
+
PE
0
1
U, V, W,
PE
5 Nm
44 lb-in
M 6
9300vec123
Fig. 5.5-7 Motor connection with KTY thermal sensor
Motor cable
Shield connection
Securely clamp shield of motor cable with the lugs
PE stud
Connection of PE cable with ring cable lug
U, V, W
Connection of motor cable with ring cable lugs
Observe correct polarity. Observe maximum length of motor cable.
9300 vector Cablecross-sectionsU,V,W,PE
Type [mm
2
] [AWG]
EVF9327 10 8
EVF9328 16 6
EVF9329 25 4
Cable cross-sections