Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Diagnostics
7
7.2
7.2.8
7.2-11
EDSVF9333V EN 3.0-06/2005
7.2.8 Diagnostics
In the ”Diagnostic” menu the two submenus ”Actual info” and ”History”
include all codes for
ƒ drive monitoring
ƒ error diagnostics
In the operating level, additional status messages are displayed. If several
messages are active, the message with the highest priority is displayed:
Priority Display Meaning
1 GLOBAL DRIVE INIT Initialisation or communication error between keypad
and controller
2 XXX - TRIP Active TRIP (contents of C0168/1)
3 XXX - MESSAGE Active message (contents of C0168/1)
4
Special controller states:
Switch-on inhibit
5
Source of controller inhibit (the value of C0004 is displayed at the same time):
STP1 Terminal X5/28
STP3 Operating module or LECOM A/B/LI
STP4 INTERBUS or PROFIBUS-DP
STP5 System bus (CAN)
STP6 C0040
6
Source of quick stop:
QSP-term-Ext Input MCTRL-QSP at function block MCTRL is at HIGH
level
QSP-C0135 Operating module or LECOM A/B/LI
QSP-AIF INTERBUS or PROFIBUS-DP
QSP-CAN System bus (CAN)
7 XXX - WARNING Active warning (contents of C0168/1)
8 xxxx Value under C0004