Commissioning
Parameter setting with the XT EMZ9371BC keypad
Commissioning example in V/f characteristic control mode
6
6.3
6.3.1
6.3-3
EDSVF9333V EN 3.0-06/2005
NoteSwitch-on sequence
18. Set your type of t he speed feedback system
”Feedback type” (C0025)
Lenze setting: 1 (no f eedback)
See chapter ”Commissioning” →
”Setting of speed feedback”
A When using a TTL encoder:
Select the encoder used under C0025
B When using a TTL encoder with a number of
increments which cannot be set under C0025:
Set C0025 = 100
Enter the number of increments under C0420
C If required, compensate a voltage drop in the
incremental encoder cable. Use C0421 to adjust the
supply voltage for the TTL encoder.
D When using a HTL encoder:
Set C0025 = 101
Enter the number of increments under C0420
19. Set the maximum speed (C0011)
Lenze setting: 3000 rpm
MB
å
NMMB
`MMNN
`MMNM
See chapter ”Commissioning” →
”Acceleration, deceleration, braking,
stopping”
20. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
= t
ir
⋅
C0011
f
2
− f
1
(see chapter ”Commissioning” →
”Acceleration, deceleration, braking,
stopping”)
21. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
= t
if
⋅
C0011
f
2
− f
1
(see chapter ”Commissioning” →
”Acceleration, deceleration, braking,
stopping”)
22. If required, set the quick stop deceleration ramp
(C0105)
Lenze setting: 5.00 s
See chapter ”Commissioning” →
”Acceleration, deceleration, braking,
stopping”
23. If required, adapt the f ixed setpoints JOG. Seecodetable
A JOG 1 (C0039/1)
Lenze setting: 1500 rpm
Activation:
X5/E3 = HIGH
B Further fixed setpoints:
JOG 2 (C0039/2) ... JOG 15 (C0039/15)
24. Ensure a powerfail-proof saving of the settings in
one of the four parameter sets (C0003)
UseC0003=1tosavethesettingsinparameterset
1.
Code C0003 is the f irst code in the
menu ”Setup V/f”.
After switching on the DC 24 V supply
or mains connection, parameter set 1 is
automatically activated.
(see chapter ”Parameter setting”)
25. Switch on the mains if the external DC 24 V supply
voltage is switched on only.
26. Enable controller
misc009
59 28
X5
}
Terminal X5/28 = HIGH
(see chapter ”Commissioning”
→”controller inhibit”)
27. Enter the setpoint
Analog setpoint
selection:
-10 ... +10 V via
potentiometer at X6/1
and X6/2
Fixed speed:
Activate JOG 1 with
X5/E3 = HIGH
JOG 1 is parameterised in C 0039/1