Configuration
Code table
8
8.3
8.3-10
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0093 DRIVE IDENT
Controller identification
z Read only
0 invalid Damaged power section
1 none No power section
9321
...
9333
9321VC
...
9333VC
Display of the controller used
C0094 PASSWORD 0 0 {1} 9999 Password
z C0094=1...9999: Free access
to the user menu only
7.2-10
C0095
Mot Io Æ 0.00 {0.01 A} 1000.00 Motor magnetising current
Æ depending on C0086, C0088
and C0091
z Change of C0086, C0088 and
C0091 sets C0095 to the Lenze
setting
z Change of C0095 sets
C0086 = 0
6.6-1
6.11-5
C0096
0 no protection No password
protection
Parameter access protection
z Extension of the access
protection for AIF bus systems
and CAN with activated
password in C0094
z All codes in the user menu can
continued to be accessed.
1 Rprotection Read protection
2 Wprotection Write protection
3 R/W protection Read/write
protection
1 AIF PROTECT. 0 Parameter access protection AIF
2 CAN PROTECT. 0 Parameter access protection CAN
C0099 S/W version
x.y
Software version
z Display only
x
y
Main version
Subversion
C0101
0.00 {0.01 s} 999.90
Additional acceleration times for
speed setpoint conditioning,
function block NSET
z Additional acceleration and
deceleration times for the
main setpoint
z Activation via binary coding of
digital input signals in
C0788/1 ... C0788/4
z For coding see description of
function block NSET
See System
Manual
(extension)
1 add Tir 0.00
2 add Tir 0.00
... ... ...
15 add Tir 0.00
C0103 0.00 {0.01 s} 999.90
Additional deceleration times for
speed setpoint conditioning,
function block NSET
z Additional acceleration and
deceleration times for the
main setpoint
z Activation via binary coding of
digital input signals in
C0788/1 ... C0788/4
z For coding see description of
function block NSET
1 add Tif 0.00
2 add Tif 0.00
... ... ...
15 add Tif 0.00
C0104
select accel. 0
Selection of acceleration function
of the linear ramp function
generator of NSET
See System
Manual
(extension)
0 a=const Constant acceleration
1 t=const Constant time
2 s=const Constant path