Troubleshooting and fault elimination
Error elimination
Error messages at the keypad or in the parameter setting program Global Drive Control
9
9.4
9.4.4
9.4-8
EDSVF9333V EN 3.0-06/2005
RemedyCauseFaultError number
x=0:TRIP
x = 1: Message
x=2:Warning
Error
code
Reversed motor phases when operating
with feedback or reversed encoder
tracks so that the direction of rotation
has changed
z Check the motor cable connection for
correct phase position
z If possible, operate the motor with
deactivated feedback (C0025 = 1) and
check the direction of rotation of t he
motor.
OH x050 Heatsink
temperature is
higher than the
value set in the
controller
Ambient temperature T
u
>40°Cor50°C z Allow controller to cool and ensure
better ventilation
z Check ambient temperature in the
control cabinet
Heatsink very dirty Clean heatsink
Incorrect mounting position Change mounting position
OH3 x053 Motor temperature
is higher than the
value set in the
controller
Motor too hot because of excessive
current or frequent and too long
acceleration
Check drive dimensioning
NO KTY is connected to X8 Connect KTY or switch off monitoring
(C0583 = 3)
OH4 x054 Heatsink
temperature is
higher than the
value set in C0122
Ambient temperature T
u
>40°Cor
50 °C.
z Allow controller to cool and ensure
better ventilation
z Check ambient temperature in the
control cabinet
Heatsink very dirty Clean heatsink
Incorrect mounting position Change mounting position
The value entered in C0122 is too low Enterhighervalue
OH7 x057 Motor temperature
is higher than the
value set in C0121
Motor too hot because of excessive
current or frequent and too long
acceleration
Check drive dimensioning
NO KTY is connected to X8 Connect KTY or switch off monitoring
(C0584 = 3)
The value entered in C0121 is too low Enterhighervalue
OH8 x058 PTC at terminals
T1, T2 indicates
motor overheating
Motor too hot because of excessive
current or frequent and too long
acceleration
Check drive dimensioning
Terminals T1, T2 are not assigned Connect PTC or thermostat or switch off
monitoring (C0585=3)
OU x020 Overvoltage in t he
DC bus
Braking energy is too high. The DC-bus
voltage is higher than set in C0173.
z Use a braking unit or regenerative
module
z When using the braking units 935x,
check the settings of the switching
thresholds (see Operating
Instructions for 9350 braking unit)
z In case of parallel connection of 935x
braking units, check the settings for
master and slave (see Operating
Instructions for 9350 braking unit)
z If possible prolong the braking ramp
(C0013, C0105)
PEr x074 Program fault An error has been detected in the
program run. The parameter set 1 is
loaded automatically. All parameter
data which have been changed before
but not saved will get lost.
Contact Lenze
PI x079 Initialisation error z A fault was detected during transfer
of parameter set between the
controllers
z Parameter set does not match the
controller
Correct parameter set