Commissioning
Operating mode
Vector control
6
6.8
6.8.2
6.8-10
EDSVF9333V EN 3.0-06/2005
C0006=1setthevectorcontrolmode.
Note!
When setting the vector control mode, the slip compensation
(C0021) is automatically set to 0.0 %.
ƒ When you switch back to the V/f characteristic control mode,
the slip compensation must be re-adapted.
The motor data of the motor nameplate must be entered:
ƒ Rated motor speed (C0087)
ƒ Rated motor current (C0088)
ƒ Rated motor frequency (C0089)
ƒ Rated motor voltage (C0090)
ƒ Motor cos ϕ (C0091)
Execute the motor data identification. ( 6.6-13)
Set vector control
Prepare the motor data
identification
Executing the motor data
identification