Configuration
Code table
8
8.3
8.3-35
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0581 MONIT EER 0
0 TRIP
Configuration monitoring EEr,
external fault
See System
Manual
(extension)
1 Message
2 Warning
3 Off
C0582 MONIT OH4 2
2 Warning
Configuration monitoring OH4,
heatsink temperature
z The operating temperature
can be set in C0122
See System
Manual
(extension)
3 Off
C0583 MONIT OH3 3
0 TRIP
Configuration of motor
temperature monitoring with
fixed operating temperature
z Only for KTY at X8
z The operating temperature is
fixed at 150 °C
6.6-10
See System
Manual
(extension)
3 Off
C0584 MONIT OH7 3
2 Warning
Configuration of monitoring
motor temperature with variable
operating temperature
z Only for KTY at X8
z When reaching the
temperature set in C0121 the
warning OH7 is activated
6.6-10
See System
Manual
(extension)
3 Off
C0585 MONIT OH8 3
0 TRIP
Configuration of motor
temperature monitoring
z Temperature monitoring via
PTC input (T1, T2)
6.6-8
See System
Manual
(extension)
2 Warning
3 Off
C0587 MONIT SD3 3
0 TRIP
Configuration of monitoring SD3,
encoder at X9
z Monitors the voltage supply at
X9/pin 8
See System
Manual
(extension)
2 Warning
3 Off
C0588 MONIT
H10/H11
0
0 TRIP
Configuration of monitoring H10
and H11, thermal sensors in the
controller
z H10: Sensor error - heatsink
temperature
z H11: Sensor error - interior
temperature
See System
Manual
(extension)
3 Off
C0591 MONIT CE1 3
0 TRIP
Configuration of monitoring CE1,
communication error at CAN-IN1
See System
Manual
(extension)
2 Warning
3 Off
C0592 MONIT CE2 3
0 TRIP
Configuration of monitoring CE2,
communication error at CAN-IN2
2 Warning
3 Off
C0593 MONIT CE3 3
0 TRIP
Configuration of monitoring CE3,
communication error at CAN-IN3
2 Warning
3 Off