Configuration
Code table
8
8.3
8.3-21
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0260 MPOT1 high 100.00 -199.99 {0.01 %} 199.99 Upper limit, function block
MPOT1
z Condition: C0260 > C0261
See System
Manual
(extension)
C0261 MPOT1 low -100.0 -199.99 {0.01 %} 199.99 Lower limit, function block
MPOT1
z Condition: C0261 < C0260
C0262 MPOT1 TIR 10.0 0.1 {0.1 s} 6000.0 Acceleration time T
ir
, function
block MPOT1
z The set time refers to a change
of 0 ... 100 %
C0263 MPOT1 Tif 10.0 0.1 {0.1 s} 6000.0 Deceleration time T
if
, function
block MPOT1
Motor potentiometer
z The set time refers to a change
of 100 ... 0 %
C0264 MPOT1 on/off 0
0 no change
Deactivation of motor
potentiometer, function block
MPOT1
z Function is executed when
MPOT1-INACT = HIGH
1 Deceleration with T
if
to 0%
2 Deceleration with T
if
to C0261
3 Jump with T
if
=0to0%
4 Jump with T
if
= 0 to C0261
5 Acceleration with T
ir
to C0260
C0265 MPOT1 INIT 0
0 Value of MPOT1 when mains fails
Initialisation of motor
potentiometer, function block
MPOT1
z Starting value which is to be
accepted during mains
switching and activated motor
potentiometer
1 lower limit of C0261
2 0%
C0267
Selection list 2 Configuration of digital input
signals, function block MPOT
See System
Manual
(extension)
1 CFG: UP 1000 FIXED0
UP DOWN MPOT1-OUT
00 ⎯
01 ↓
10 ↑
11 ⎯
↑: Output signal runs to the upper limit
value
↓: Output signal runs to the lower limit
value
⎯: Output signal is unchanged
2 CFG: DOWN 1000 FIXED0
C0268
CFG: INACT 1000 FIXED0 Selection list 2 Configuration of digital input
signal, function block MPOT
z HIGH: motor potentiometer is
not active. Output signal runs
to 0
C0269
Digital input signals, function
block MPOT
z Display of the signals linked in
C0267 and C0268
1 DIS: UP
2 DIS: DOWN
3 DIS: INACT