Installation
3-37
Part 1128350_02
E 2020 Nordson Corporation
Input Parameters
Table 3-4 Input Parameters
Selection Functions Hardware Option Required
Disabled Input not used N/A
Setback Control
S Active state causes the system to go into setback
S Deactivated state causes system to return to set point
temperature
N/A
Heater Control
S Active state turns heaters on
S Deactivated state turns heaters Off
N/A
Pump Control
S Active state turns pump on
S Deactivated state turns pump Off
N/A
Automatic Setback When active signal removed, system goes into Automatic
Setback after Auto Setback Start Time elapses.
N/A
Fill Control
S Active state turns on fill system
S Deactivated state turns fill system Off
Fill System
Flow Monitor Enables flow monitoring when active Flow Board and License
System Enable
S When active, allows system to operate normally.
S When deactivated, heaters, pumps and pattern
outputs are off. Prevents system from moving from
Idle to Run.
N/A
Remote Recipe 0
Remote recipe recall inputs can be configured for 2, 3, 4
or 5 binary weighted inputs:
2Inputs=3recipes
3Inputs=7recipes
4inputs=15recipes
5inputs=31recipe
Recipe inputs = 0 is reserved for UI recipe selection
Customer will select the number of inputs to dedicate and
the inputs will be automatically assigned.
Legacy I/O or Expanded I/O
Remote Recipe 1 Legacy I/O or Expanded I/O
Remote Recipe 2 Legacy I/O or Expanded I/O
Remote Recipe 3 Legacy I/O or Expanded I/O
Remote Recipe 4 Legacy I/O or Expanded I/O
SA Pump Reset Used for Single Acting Pumps to reset the pump between
products.
Single Acting Pump