To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
Then continuously from
Dx1000, example:
5378 mm, CRLF mode
+0005378<CR><LF>
…
Switching off continuous, permanent distance value output
Table 19: Example: Switching off continuous, permanent distance value output
To Dx1000
<STX>sMN SetAccessMode 4 81BE23AA<ETX>
From Dx1000
<STX>sAN SetAccessMode 1<ETX>
Continuous output of
Dx1000 stops
To Dx1000
<STX>sWN rs422PeriodicOutputContent 0<ETX>
From Dx1000
<STX>sAN rs422PeriodicOutputContent<ETX>
To Dx1000
<STX>sMN mEEwriteall<ETX>
From Dx1000
<STX>sAN mEEwriteall 1<ETX>
To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
Setting preset value to 10 m
Table 20: Example: Setting preset value to 10 m
Designation Syntax
To Dx1000
<STX>sMN SetAccessMode 4 81BE23AA<ETX>
From Dx1000
<STX>sAN SetAccessMode 1<ETX>
To Dx1000
<STX>sWN preset 2710<ETX>
From Dx1000
<STX>sWA preset<ETX>
To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
Executing preset
Table 21: Example: Executing preset
Designation Syntax
To Dx1000
<STX>sMN SetAccessMode 4 81BE23AA<ETX>
From Dx1000
<STX>sAN SetAccessMode 1<ETX>
To Dx1000
<STX>sMN activatePreset<ETX>
From Dx1000
<STX>sAN activatePreset<ETX>
To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
3.7.4 Ethernet interface
The Ethernet interface enables setting of the device parameters as well as monitoring
and control of the device. If desired, measurement data (e.g. distance, speed or signal
level values) and operating data (e.g. inside temperature, operating hours or device sta‐
tus) are transmitted.
No continuous data output is possible via the Ethernet interface.