Installation and EMC guidelines
1.10 Control cabinet
SIMATIC TDC hardware
20 System Manual, 08/2017, A5E01114865-AL
1.10
Control cabinet
All control cabinets must be equipped with a grounding/equipotential busbar that must be
connected directly to the cabinet frame at both ends.
It is not allowed to operate contactors without protective circuit in a control cabinet
containing SIMATIC TDC components.
If contactors without protective circuit are operated in a control cabinet next to the
SIMATIC TDC cabinet, the cabinets must be partitioned by means of a sheet steel panel.
All control cabinets in which SIMATIC TDC components are operated must be equipped
with a shielding busbar that must be connected directly at both ends to the cabinet frame.
It is not allowed to use gas discharge lamps in the cabinet.
The cabinet must be designed to enable unobstructed air convection.